The most likely reason is that
PPKOP-501 is in the Armed state.
To provide local point control mode
access (using the Exit button and the “Proximity” card)
it is necessary to apply for this PPKOP-501 from the automated workplace of the DPU
command Disarm.
Reason for failure of PPKOP-501 control commands
to close the locks is the translation of the module
SLZ concentrator into emergency mode, in which
unlocking of locks at all points is ensured
access.
To restore the operation mode of access points
it is necessary to transfer the hub module from the workstation DPU
SLZ in normal mode.
Communication between SLZ and PPKOP-501 devices is carried out via
address line of the RS-485 interface. All Control Panels
connected to the line in parallel. Malfunction
the input circuit of one of the devices can serve
the reason for the lack of communication with others
devices.
To localize a device with a faulty RS-485 port
required:
• Disable the communication line between the hub module
and PPKOP-501.
• Measure constants with a digital multimeter
voltage at terminals A and B relative to the GND terminal
concentrator module connection boards (PPMC). On
terminal A, the voltage level should be within
within UA=2.8±0.15 V. At terminal B the level
voltage should be within UA=1.9±0.15
V.
• Connect PPKOP-501 to the line one by one,
controlling voltage levels UA and UB. If at
connecting another device, measured levels
voltages at terminals A or B will differ from
mentioned above, you need to turn off this device
from the line and repair the RS-485 port.
• After disconnecting a device with a faulty port
the remaining devices must restore communication with
SLZ concentrator module.
Reasons for receiving this notice at the automated workplace of the DPU
may be:
• Malfunction of the magnetic contact detector,
device included in the AL circuit 1
Actions: Check serviceability
magnetic contact detector. Check
AL resistance.
• Insufficient time for the “Open state” parameter
doors", specified in the database of this device in the workstation
DBA.
Actions: Check this parameter by sending
on this device the command “Request the parameter “Time”
door open state" from the Engineer's workstation. When
need to adjust this parameter in
database and write it to the device.
The serviceability of the lock is monitored by a built-in lock
Hall sensor connected to the AL 4 circuit
PPKOP-501. Reason for receiving this notice
there may be incorrect operation or malfunction
this sensor.
It is necessary to check the mutual installation and availability
dirt on the armature and lock body, check
AL parameters. If a malfunction is detected
sensor, replace the lock.
You need to check the connection via
local network of a computer with installed workstation
Video client and video server SLZ.
All workstation computers must have Video
Windows Firewall is disabled.
The reason for the periodic loss of voltage on
the output of the power supply may be
cooling fan failure block
power supply, resulting in overheating,
thermal protection is triggered and shutdown occurs
output voltage. After the decrease in internal
power supply temperature control circuit connects
output voltage.
To ensure operation of the power supply it is necessary
Restore cooling fan operation:
Clean and lubricate the bearings or replace them with new ones.
The Proximity card reader is connected to
Computer workstation Engineer via TM-USB adapter.
Identification numbers are read
via a virtual COM port whose number
can be determined in Device Manager:
Ports (COM and LPT) → USB Serial device (COM X) , where X is the number of virtual
consistent
port.
This number must be entered in the AWS settings
DBA: File → Settings → Ports →
COM port number X.
It is necessary to check the reliability of the screen connection coaxial cable to the GND terminal of the device connection of a video camera (UPVC), as well as reliability connecting a twisted pair signal line to the terminals B- and B+ UPVK and connection board PVS-8.
Possible reasons for the lack of speech signal in
telephone handset AWP DPU:
• incorrect choice of DPU connected to the automated workstation
of the intercom used in the settings
Sound recording
• incorrect choice of DPU connected to the automated workstation
of the intercom used in the settings
virtual phone software "Pakhra"
• microphone signal level control on the virtual
the tube is in its lowest position
• recording level control built into Windows
settings is in the lowest position
On the workstation monitor, Video Client must be selected for
viewing in single camera mode required
video camera. Select the date and time on the monitor screen
video recordings. Click the play button in the form
green triangle.
After downloading the selected video fragment from the archive
Video servers on the workstation Video client are activated on it
viewing and recording control buttons.
Click the button with the image of a floppy disk Save
video fragment to file (second from right). In the opened
window, specify the file name and recording path
video fragment.
Play the recorded video on your computer possible using a special program Player.exe. Must be copied to this computer in one folder files Player.exe And playm4.dll (located on the installation disk in folder Player). Run file Player.exe and select a file to view, specifying the file type All Files (*.*).
Parameters have been reset repeater to factory settings. It is necessary to re-introduce the composition of the system object device built into the repeater and set all its parameters through the automated workplace.
Parameters have been reset repeater to factory settings. It is necessary to re-introduce the composition of the system object device built into the repeater and set all its parameters through the automated workplace.
Parameters have been reset repeater to factory settings. It is necessary to re-introduce the composition of the system object device built into the repeater and set all its parameters through the automated workplace.